Product Catalog

Standard Air-Cooled Rectifier

View PDF  |  Add to Cart

Description

The Standard series of Air-Cooled Rectifiers provide an economical alternative to the Custom and Automatically controlled rectifier lines.

 

 

 

 

 

 

Combining a lighter gauge enclosure with a chassis pan method of component layout results in a cost-effective rectifier. Incoming AC power is stepped down, isolated and rectified to a controlled DC output. Input-overload and short-circuit protection are provided by magnetic-trip breakers; output protection by means of one-time fuses in the transformer secondary. Primary AC/DC surge protection and secondary surge protection provided by disk-style M.O.V’s. Output control using 25-steps of tap adjustment, gives ample control to output settings. A single meter, switched between amperes and volts, is supplied as standard construction, with extra meters available optionally. The Standard series of rectifiers has made available a basic, economical rectifier for cost effective cathodic protection systems.

Features
  • Heavy duty, removable, chassis with lift-off case for full access (larger units only)
  • Wall or pole mounting (floor mounting optional)
  • Single, switched, “Press-to-Read” DC meter
  • AC / DC surge protection on all models (M.O.V’s)
  • Transformer constructed to Class “H” temperature requirements. Minimum efficiency of 95%
  • CSA certified under File No.: LR-45382
  • All brass/copper hardware finished in electrolessnickel plate for superior corrosion prevention. All other hardware is stainless steel
  • One year warranty, from date of purchase, against defective components and faulty workmanship
  • Commonly used options available to tailor the Standard Rectifier to specific requirements
  • Available in three door or fixed two door enclosure

Specifications
  • Single phase inputs only: Single phase inputs only: 115, 208, 115/230, 115/460, 230, 230/460, 460, and 600 VAC., 60 Cycle (50 Hz. optional) VAC.
  • Minimum 25-steps of terminal block tap adjustment
  • Magnetic trip input circuit breakers and rectifier fuses for full overload and short circuit protection
  • Output voltage range from 12 to 120 volts DC
  • Output current range from 4 to 100 amperes DC
  • Special output or input ratings available on request
  • Metering: 2% meters, temperatur compensated
  • Operating ambient: -58°F to 113°F (-50°C to +45°C).
  • Cooling by natural air convection
  • Cabinet rated NEMA 3R; constructed from 14 gauge galvanized steel, finished with 3-5 mils fusion bond polyester powder paint, white.